PV1-F 2PfG 1169 1800V DC PV solar cable wire Single 1 Core 1.5~35mm2 kabel TUV Approved kablo
Application
Suitable for nominal DC voltage 1.5KV(Between conductor to conductor or conductor to earth) solar power system.
Double insulation, electron-beam cross-linked cables for photovoltaic powerstation Construction
Conductor.Tinned copper, according to the VDE
0295/IEC 60228, Class 5
Insulation:Polyolefincopolymerelectron-beamcross-inked
Outersheath:Polyolefincopolymerelectron-beamcross-linked
Sheath color:Black/Red/Blueoraspercustomer'srequest
Nominalvoltage:Uo/U=600/1000VAC, 1800VDC
Voltage test on completed cable:6.5kVAC, 15kVDC, 5min
Ambient temperature:-40Cup to+90°C
Max.Temperature at conductor:+120°C
The expected period of use is 25 years(Ambiet temperature:-40°Cup to+90℃)
The permitted short-circuit-temperature refer to a
period of 5sis+200°C
Bending radius:≥4XOD(OD<8mm) ; ≥6×OD(OD≥8mm)
Resistanceagainstacidandalkalinesoluton:EN60811-2-1
Coldbendingtest:EN60811-1-4
Weathering/UV-resistance:HD605/A1
O-zoneresistanceatcompletecable:EN50396
Firetest:IEC60332-1Smoke density:IEC 61034, EN 50268-2
Contentofhalogenacidgas:IEC670754-1EN50267-2-1
Material Properties/Standards
Fire-resistanceperformance:IEC60332-1
Smokeemission:IEC61034:EN50268-2
Low fire load:DIN 51900
Approvals:TUV2PfG1169/08.2007 PV1-F
Application standards:UNE 21123; UNE 20.460-5-52, UTEC 32-502
Cross section 2 (mm ) | Conductor constuction (n/mm) | Conductor Stranded OD. (mm) | Cable OD. (mm) | Conductor Max. Resistance AT 20°C(Ohm/km) |
1.5 | 30/0.25 | 1.58 | 4.90 | 13.7 |
2.5 | 49/0.25 | 2.02 | 5.20 | 8.21 |
4.0 | 56/0.285 | 2.50 | 6.00 | 5.09 |
6.0 | 84/0.285 | 3.17 | 6.30 | 3.39 |
10 | 84/0.385 | 4.56 | 8.00 | 1.95 |
16 | 128/0.40 | 5.60 | 9.60 | 1.24 |
25 | 192/0.40 | 6.95 | 11.40 | 0.769 |
35 | 276/0.40 | 8.74 | 13.20 | 0.565 |
Advantages
Electron-beam cross-linked compounds
UV, ozone and hydrolysis resistant
High temperature resistant, the materials do not melt or flow
Good cold flexibity
Very long service life>25 years at 90℃
Compatible to all popular connectors
Other related cables and connectors:
Solar PV MC4 connectors, branches and lead extension wire harness.
AC Aluminum/Copper XLPE/PVC Amoured/un-armoured Power Cable