Energy Storage Cable

  • 1500V Energy Storage Cable Wire 2 layer XLPE Insulation kabel 2 PfG 2693 TUV Approved kablo​
  • 1500V Energy Storage Cable Wire 2 layer XLPE Insulation kabel 2 PfG 2693 TUV Approved kablo​
  • 1500V Energy Storage Cable Wire 2 layer XLPE Insulation kabel 2 PfG 2693 TUV Approved kablo​
1500V Energy Storage Cable Wire 2 layer XLPE Insulation kabel 2 PfG 2693 TUV Approved kablo​1500V Energy Storage Cable Wire 2 layer XLPE Insulation kabel 2 PfG 2693 TUV Approved kablo​1500V Energy Storage Cable Wire 2 layer XLPE Insulation kabel 2 PfG 2693 TUV Approved kablo​

1500V Energy Storage Cable Wire 2 layer XLPE Insulation kabel 2 PfG 2693 TUV Approved kablo​

  • Conductor: Bare Copper
  • Insulation: XLPE
  • Sheath: XLPE
  • Rated voltage: 1.5kV DC
  • Product description: 1500V Energy Storage Cable Wire 2 layer XLPE Insulation kabel 2 PfG 2693 TUV Approved kablo​ Conductor: EN60228Class5soft annealed stranded copper Insulation: Electron-beamcross-linked materials wit
  • INQUIRY

1500V Energy Storage Cable Wire 2 layer XLPE Insulation kabel 2 PfG 2693 TUV Approved kablo


Approvals

TUV Certification 2PfG 2693/06.19 all color
4.0-240mm²


Technical data




Conductor: EN60228Class5soft annealed stranded copper

Insulation: Halogen-free Low Smoke Flame Retardant

Cross linked Polyolefin Material at 125

with RoHS compliance

Jacket: Halogen-free Low Smoke Flame Retardant

Cross linked Polyolefin Material at 125with RoHS compliance

Rated voltage: 1000VDC, 1500VDC

Test voltage: 1000VDC=5000V, 5Min1500VDC=5000V, 5Min

Ambient temperature: -40up to+125

Insulation volume resistivity: 1x 102.cm

Low temperature impact test: -40±2*16h, compliance with the EN 60811-506 standard

Low temperature bending test: (Cable outer diameter12.5mm) -40±2*16H, in accordance with EN 60811-504; without cracking

Shrinkage test: ComplywithEN60811-503, 200, 1H, shrinkage2%

High temperature pressure test: EN60881-508

Wet heat test: 85*1000h, humidity 85%,

compliance with EN 60068-2-78 standard; (Outdoor Use)

Acid resistance test: ISO6722-1(Indoor)

Acid-alkalitestEN60811-404; Oxalicacidsolutin

(0.5mol/L) ,  Lipuorsodiihydroxid(1mol/L) (Outdoor Use);

Halogen content test:  EN 50525-1 ANNEX B (Indoor)

Smoke density(Suitable for low smoke without halogen cable):  EN 61034-2 Light transmittance 260%

FlameretardanceEN60332-1-2(Wholewire)(Indoor)

Artificial climate aging test

TUV accreditation 2PfG 2693/06.19

Salt spray test(when applicable): IEC 60068-2-11and2PfG 2693, Clause 8.3.12


Cross section (mm2 ) Conductor constuction (n/mm) DC 1000V,ESP10Z3Z3-K 125°C ESL10Z3Z3-K 125°C DC1500V,ESPl5Z3Z3-K 125°C ESL15Z3Z3-K 125°C Conductor Max.Resistance AT 20°C (Ω/km)
Insulation Ave.Thic. (mm) Jacket Ave.Thic. (mm) Nominal average outer diameterof finished Cable(mm) Insulation Ave.Thic. (mm) Jacket Ave.Thic. (mm) Nominal average outer diameterof finished Cable (mm)
4.0 56/0.285 0.50 0.40 4.80 1.20 1.30 7.60 5.09
6.0 84/0.285 0.50 0.60 5.80 1.20 1.30 8.00 3.39
10.0 397/0.16 0.60 0.70 7.60 1.40 1.30 9.80 1.95
16.0 513/0.20 0.70 0.80 8.70 1.40 1.30 11.00 1.24
25.0 798/0.20 0.70 0.90 10.20 1.60 1.30 12.60 0.795
35.0 1121/0.20 0.80 1.00 12.20 1.60 1.30 14.30 0.565
50.0 1596/0.20 0.90 1.10 14.50 1.60 1.40 15.80 0.393
70.0 2220/0.20 1.00 1.10 16.50 1.60 1.40 18.00 0.277
95 2997/0.20 1.20 1.10 18.60 1.80 1.40 20.40 0.210
120 950/0.40 1.20 1.10 20.40 1.80 1.40 22.20 0.164
150 1185/0.40 1.40 1.20 23.00 2.00 1.50 24.50 0.132
185 1473/0.40 1.60 1.40 26.50 2.00 1.60 27.30 0.108
240 1903/0.40 1.70 1.40 28.60 2.20 1.70 30.00 0.0817